Mode | The factory code | Lightning arrester rated voltage kV RMS | Lightning arrester system nominal voltage is kV RMS | Continuous operating voltage of arrester kV RMS | DC reference voltage kV is not less than 1mA | Impulse current residual kV is not c than peak | Nominal current impulse residual voltage kV is not hollow insulator than peak | Steep impulse current residual kV is not hollow insulator than peak | 2ms square wave through flow capacity of A 20 peak | Nominal creepage distance mm | Weight kg | Remarks |
Y10WDB1-631/1068W | 62920 | 631dc | 515dc | 631/4 | 936 | 1068 | 4000 | 32000 | 4210 | |||
Y20WDB1-132/289W | 62925 | 132r.m.s | 50 r.m.s | 188/4 | 278 | 289 | 8000 | 4100 | 687 | |||
Y5WE1-145/358W | 62929 | 145r.m.s | 107 r.m.s | 210/4 | 358 | 8000 | 5100 | 680 | ||||
YH20WDB1-1010/1625 | 82900 | 1010 | ±800 | 824dc | 1010/4 | 1391 | 1625 | 8000 | 45320 | 2871 | ||
YH2WCBH1-1083/1450 | 82901 | 1083 | ±800 | 889dc | 1083/4 | 1402 | 1450 | 8000 | 13286 | 2127 | ||
YH2WCBL1-566/770 | 82903 | 566 | ±800 | 454dc | 566/4 | 734 | 770 | 8000 | 7112 | 837 | ||
YH20WEM-278/431 | 82913 | 278 | ±800 | 666dc | 813/4 | 1036 | 1088 | 8000 | 10248 | 1893 | ||
YH2WML-364/504 | 82914 | 364 | ±800 | 298dc | 364/4 | 494 | 504 | 4000 | 4172 | 606 | ||
YH20WDB1-1400/2125 | 82907 | 1400 | ±1100 | 1190dc | 1400/4 | 1826 | 2125 | 8000 | 56160 | 3418 |